What a correction letter looks like
After first review, SDCI sends a single correction letter consolidating comments from each reviewing discipline:
- Zoning — height, FAR, setbacks, lot coverage, departures.
- Structural — engineer's calc clarifications, load path, foundation retrofit details.
- Energy — alteration compliance, air-barrier transition, equipment sizing.
- Substantial alteration (if triggered) — checklist items per SDCI Tip 314.
- ECA (if applicable) — buffer compliance, geotech follow-through.
- Tree (if triggered) — protection plan revisions.
Each comment needs a written response and (usually) a drawing revision.
How long this takes
- First review: 4–8 weeks after intake.
- Each correction round: 4–6 weeks (your turnaround + SDCI re-review).
- Total cycles: 1–3 is typical for an addition with experienced design team. The substantial-alteration threshold is a common reason to go to a second round.
How to keep this short
- Use a designer with recent SDCI addition permits. Their previous correction letters tell them what current SDCI reviewers ask for.
- Turn corrections around fast. SDCI's clock is on them; yours is on you. Two-week turnarounds keep the project moving.
- Address every comment, even minor ones. Skipping a comment guarantees it comes back next round.
- Get the substantial-alteration question settled in round one. This is the single biggest time-killer if it's left ambiguous.
When this ends
When the correction letter comes back with no comments, SDCI issues the building permit. You pay the remaining 25% of the permit fee, plus any sub-permit fees still outstanding, and the permit is "issued" — the GC can mobilize.
Go deeper
Optional reading. Skip if you only need the headline.
›How to structure a correction response so the next cycle is shorterThe response-letter format Seattle designers use to close corrections in one round instead of three.
The response letter format
When the reviewer re-opens your project, they read the correction letter and then look for the response. If the response is scattered across email threads or buried in sheet notes, the reviewer re-issues the comment. The file should contain a single correction response letter that mirrors the structure of the SDCI comment letter exactly.
For each numbered comment, include three things in order:
- The original comment, verbatim. Don't paraphrase — reviewers look for their own wording first.
- The response. One of four stock framings:
- "Revised — see sheet A2.1, detail 4, revision cloud 3." (Most comments.)
- "Acknowledged — the condition does not apply because [narrow, specific reason]." (Use sparingly; every one of these is a fight you're choosing.)
- "Clarification added — see general note on A0.0." (For anything a reviewer flagged as "ambiguous.")
- "See attached calc / memo from [engineer], dated [date]." (For structural or energy comments that need a discipline response.)
- A direct pointer to where the change lives: sheet number, detail number, revision cloud number. Never "see revised drawings" — always the exact location.
Revision clouds and deltas
Every drawing change goes inside a revision cloud, with a delta triangle pointing to the revision number in the title block. The title block revision log should match the response letter's revision number. Reviewers scan for that match first; if the delta doesn't match the response, the comment reopens.
What experienced designers do differently on additions
- They settle the SDCI Tip 314 substantial-alteration question in round one. If the project is near the threshold, the first submittal should explicitly state the calculated alteration value as a percentage of building replacement cost, and the conclusion. Leaving this ambiguous reliably adds a cycle.
- They front-load existing-conditions documentation. Reviewers ask for verification of existing wall types, existing foundation, existing electrical service. A first submittal with photos and an inspection narrative for each major existing condition heads off a cycle of "please verify."
- They pick their fights. One or two pushback comments in the response letter is normal. Five is adversarial and usually costs a cycle.
What to hand the reviewer on resubmittal
- Revised drawings (full set), with revision clouds and the revision log updated.
- The correction response letter (PDF).
- Any new supporting calcs, memos, or product data as separate PDFs (referenced from the response letter by filename).
- A cover note confirming no scope changes outside the correction comments — reviewers re-scope if they find changes they didn't ask for.
Where this information came from
- SDCI — Construction Permit: Addition or Alteration · retrieved April 23, 2026
- SDCI Tip 314 — Substantial Alteration of Existing Buildings · retrieved April 23, 2026
- SDCI Tip 100 — Building Permit Application Submittal Requirements · retrieved April 23, 2026
- L&I — Verify a Contractor · retrieved April 23, 2026
- EPA — Renovation, Repair and Painting (RRP) Rule · retrieved April 23, 2026
- WA Department of Labor & Industries — Asbestos in Construction (WAC 296-62-077) · retrieved April 23, 2026